WaratahBoilers
"Supporting Australia's production"

HOTWATER BOILERS       


Waratahs range of boilers employ a well tried and proven design concept based on the reverse flame combustion.This reverse flame combustion method provides an economical and highly efficient three pass gas flow system. The design incorporates a large pressurized combustion chamber allowing the first two passes of gas to be made in the combustion chamber itself. The scrubbing action of the reversing flame causes  the gases to enter and re-enter the high temperature flame zone many times before making the third and final pass through the smoke tubes. Dimples in the smoke tubes further slow the passage of the combustion gases providing additional efficient heat transfer.

A major criteria in this design is the careful balance between radiant heating surfaces and secondary convection heating surfaces to ensure optimum efficiency when firing either gas or oil.

Because of the use of a pressurized combustion system the boiler operation is completely independent of chimney draught. Chimney sizes are therefore reduced with consequent installation savings.

An extremely easy to clean design as all heating surfaces can be reached easily by opening the burner door. This boiler can be cleaned while hot and still in service completely eliminating the need to shut down the system. An important feature of continued efficient operation, as each millimetre of soot or fouling reduces efficiency by 7%.

Wet back construction with insulated firing door for maximum heat retention to reduce the possibility of condensation in the combustion chamber.

A completely demountable casing system which is easily mounted on the framework forming a permanent part of the boiler.

The boiler top casing is strengthened and braced. The top section is constructed of heavy chequer plate and can serve as a walkway overcoming the most common on site damage problem.

FEATURES

Output Range
100kW to 3000kW - higher outputs on request

Working Pressure
500kPa

Test pressure
750kPa

Insulation
Boiler Shell:
50mm fibreglass insulation with aluminium foil totally encasing boiler shell
Boiler Door: Ceramic Fibre

Casing
1mm steel panels finished in blue enamel
3mm chequer plate top

Door Hinging
Door hinged both sides - handling therefore optional

Firing Equipment
Matching over-fire forced draft pressure jet burner to suit nominated fuel system
Natural Gas/LPG/Oil/Duel Fuel

Electrical Wiring
400 volt 3 phrase 50 cycle standard
Except models WW100 - WW300: 230volt 1 phrase 50 cycle

Valves
Drain valve fitted as standard
Safety valve sized to suit application optional

Control Panel
Standard modular control panel mounted on front of top plate

Standard Features Optional Features
 
ON/OFF Switch
Digital Flow
Temperature Indication
Control and High Limit
Thermostats
High/Low Thermostat
Indication Lights
Power On
High Limit
Lock Out
High Fire
Low Fire
Digital Return
Temperature Indication
Flue Gas Temperature Indication
Modulating Control
Low Water
Cut Out and Indication
High or Low Gas
Pressure Indication
Time Clock
 

TECHNICAL DATA

Model Output

Dimensions (mm)

WW kW A B C D E F G H J
WW100 100 770 1780 905 400 680 720 120 75 475
WW125 125 770 1780 905 400 680 720 120 75 475
WW150 150 770 1780 905 400 680 720 120 75 475
WW175 175 770 1780 905 400 680 720 120 75 475
WW200 200 930 1850 1065 400 750 870 120 85 555
WW250 250 930 1850 1065 400 750 870 120 85 555
WW300 300 930 1850 1065 400 750 870 120 85 555
WW350 350 930 1850 1065 400 750 870 120 85 555
WW400 400 930 1850 1065 400 750 870 120 85 555
WW500 500 1040 2082 1175 400 982 955 140 95 610
WW600 600 1040 2082 1175 400 982 955 140 95 610
WW800 800 1200 2172 1350 500 922 1105 140 105 705
WW1000 1000 1240 2386 1390 500 1136 1120 140 105 725
WW1200 1200 1350 2386 1500 500 1136 1205 175 125 780
WW1500 1500 1485 2490 1640 500 1240 1320 175 125 860
WW1800 1800 1660 2800 1800 500 1650 1360 175 125 940
WW2100 2100 1850 3280 2000 500 2000 1550 175 175 1045
WW2500 2500 1850 3550 2000 500 2294 1550 175 175 1045
WW3000 3000 2150 4000 2300 500 2750 1900 175 175 1200

 



 

Model

Connections (mm)

Dry Weight Water Content Fuel Consumption
WW Flow & Return Safety Vent Flue OD kg litres GAS
mj/hr
OIL
l/hr
WW100

65

20 150 445 330 430 12
WW125

65

20 150 465 322 537 14
WW150 65 20 180 485 316 645 18
WW175 65 20 180 504 312 753 20
WW200 65 25 200 650 450 860 25
WW250 65 25 200 680 440 1075 28
WW300 80 32 200 765 420 1290 35
WW350 80 32 200 780 410 1505 41
WW400 80 32 200 790 400 1670 46
WW500 100 40 250 1000 500 2150 58
WW600 100 40 250 1260 630 2580 70
WW800 125 50 300 1500 725 3225 87
WW1000 125 50 350 1796 912 4085 113
WW1200 125 2x40 400 2054 1170 5160 143
WW1500 150 2x40 450 2952 1570 6450 179
WW1800 150 2x50 450 3400 1890 7740 215
WW2100 150 2x50 500 4200 2200 9030 250
WW2500 200 2x65 600 4450 2630 10750 299
WW3000 200 2x65 600 5780 3150 12900 350